Specifications: 

Analog Input Channels

  • RTD input range: -200-850 deg C
  • RTD overall accuracy: .05% or .5 deg C
  • A/D resolution 16 bits (0.003%)
  • Temperature coefficient +/- 50 ppm per °C (span and offset)
  • RTD Type: 100 Ohm Platinum
  • RTD Alpha: .00385 or .00392
  • RTD Connections: 2 or 3-wire
  • Scan time: 550 ms for all 10 channels
  • Max lead wire resistance: 100 Ohms per side balanced
  • RTD excitation current:  250uA pulsed to reduce self-heating

Serial Ports 

RS-485 port, Screw terminals (485+, 485-, GND) (2-wire half-duplex, isolated) 
Isolations voltage, 150V 
RS-485 networking, Up to 32 (full-load) stations 
RS-485 distance, Up to 0.5 miles (baud rate dependent) 
Baud Rates from 150 to 57,600 baud 
Protocols: master and slave: Sixnet® and Modbus RTU / ASCII 
Diagnostic LEDs: Transmit (TD) and Receive (RD) 

Environmental

  • Operating temperature: -40 to 75°C 
  • MTBF: 1,294,803 Hours GB @ 40°C per MIL-HNDBK-217F2

Configuration

  • Configured using Sixnet I/O Tool Kit
  • Graphical User Interface (GUI)